Relay Design
The relay compares phase angle between two voltage signals
The relay design is analyzed in next few slides by considering following three fault conditions
F1- fault beyond the relay reach
F2 โ fault inside the relay reach
F3- fault behind the relay location- ย reverse fault
The relay operates and trips (opens CB) the ย line only if the measured impedance is less ย than or equal to setting of ZL.
RELAY CHARACTERISTICS
Protected Line โ A-B; Impedance ZL (referred to the Secondary of CT and PT)
Relay location โA Set to detect faults up to B
Fault f1, f2 are in front of the relay
Faultย f1 is outside the line section A-B
Fault f3 is behind the relay
Fault at f1 โ External to the line section A-B
ZL1 >ZL ;
Relay input: voltage V and Current I
V-IZL and V are in phase
Relay is set to block if V and V-IZL are in phase
Fault at f2 โ internal to the line section A-B
ZL2 <ZL ;ย
V-IZL and V are 180 egreeย out of phase
Relay is set to trip
if V and V-IZL are 180 degree out of phase
Fault at f3 โ Reverse fault-external to the line section A-B
ZL2 <ZL (or ZR);
Relay input: voltage V and Current I
V-IZL and V are in phase
Relay is set to block if V and V-IZL are in phase
Relay โ Phase comparator
Trip if :=
Angle between S1 – V and S2=V-IZC > 90 degree
V is Vf at relay and I = If at relay
Z = Zf=fault impedance
Zc is characteristic setting reach of relay
Relay โ Phase comparator
Relay โ Phase comparator-SELF POLARISED MHO
Relay โ Phase comparator
Mho distance phase comparator โ cross polarized
Characteristic Angle
OTHER CHARACTERISTICS
REACTANCE
OHM:-
Types of Faults in Three Phase System
Phase to ground faults- A-G,B-G,C-G
Phase-Phase faults โ A-B, B-C, C-A
Phase to phase to Ground โA-B-G, B-C-G,C-A-G
Three phase fault with/ Without Ground
Cross Country faults โ Two single line to groundย faults on different phases and at Different locations
Relay(Comparator) Inputs
The goal is to measure the same impedance up to the ย fault point irrespective of the type of fault
Relays measure the positive sequence impedance of ย the line up to the fault point
Phase to ground distance elements
A-G Fault :ย ย VA and IA + K0*IN
B-G Fault ;ย ย VB and IB + K0*IN
C-G Fault :ย VC and IC + K0*IN
Phase โ Phase Fault
A-B Fault :ย ย VAB and (IA-IB)
B-C Fault :ย ย VBC and (IB-IC)
C-A Fault:ย ย VCA and (IC-IA)
Total distance elements (units)
Six distance elements are needed to detect all types of faults.
Apparent impedance of fault loops
6 fault loops measured for each zone fault Types
Phase-to-ground
Phase-to-phase
Two phase-to-ground
Three phase
Apparent impedance of fault loops
Phase-to-phase
Apparent impedance of fault loops
Phase-to-ground
Apparent impedance of fault loops
Phase-to-ground. For Ph-E fault on phase-A
The voltage Va at relay point is
Va= Ia1 Z1 + Ia2 Z2 + Ia0 Z0
Ifย Z1ย ย =ย Z2, ย then
Va= Ia1 Z1 + Ia2 Z1 + Ia0 Z0
The current Ia at relay point is
Ia= Ia1 + Ia2 + Ia0
The Residual current at relay point
Inย = Ires = Ia + Ib + Ic = 3 * Ia0
Ifย Z1ย ย =ย Z2, ย then
Va= Ia1 Z1 + Ia2 Z2 + Ia0 Z0
Va= Ia1 Z1 + Ia2 Z1 + Ia0 Z0 + IaoZ1 – IaoZ1
Va= Z1 * ( Ia1 + Ia2 + Ia0ย ) + Iaoย * (Z0 – Z1)
Va= Z1 * ( Ia ) ย + Iao * (Z0 – Z1)
Va= Z1 * [ Ia + Iao * (Z0 – Z1)/Z1 ]
Va= Z1 * [ Ia + 3Iao * (Z0 – Z1) / 3Z1 ]
Va= Z1 * [ Ia + 3Iaoย * (Z0 – Z1) / 3Z1 ]
Va = Z1 ( Ia + 3ย Ia0 (Z0 – Z1)/3Z1)ย ย
Va = Z1 ( Ia + KN * Ires)
Where, Z1 =ย Va / ( Ia + KN* Ires)ย &ย And KN = (Z0 – Z1)/3Z1
Phase-to-ground
TWO FACTORS USED FOR I0 ZERO SEQUENCE ย COMPENSATION
VA= ZL1 & [ IA +KN*Ires ]
Ground Reach is set in Terms of ZL1 & KN
ZG=ZL1*(1+KN)
