DISTANCE PROTECTION PART – III

Errors in line impedance measurement

  • Instrument transformer Errors
  • CT errors and PT errors
  • Relay design tolerance

Line impedance calculation errors

Relay with reach setting ZAB for line between stations A & B may operate for faults beyond bus B

The relay is set to operate without any delay for faults   up to 80-85% of the protected line section impedance, ZAB. This is also called Under reaching zone or Zone1

15-20% of the remaining line section is protected by a second set of relay. These relay zone is set to reach  20-25% beyond the bus B. This is also called Overreaching Zone or Zone 2.

The Zone 2 tripping is always time delayed to coordinate with remote end breaker and line relays

Zones of Protection

Stepped Distance Scheme

Zone 1(Under reaching Zone)– Typically set to 80-85% of the protected line impedance. This conservative   approach prevents relay from operating for faults  beyond the line section

Zone 2(overreaching Zone) – At least 115% of the line   impedance to account for errors. – typical setting; 125-150% of the protected line impedance.

Zone3 (Over reaching Zone) – Typically to cover 125- 150% of adjacent line

Apparent Impedance (Infeed Under Reach Effect)

Impedance Seen by Relay at ‘A’ is ZAf  = ZA+Zf 

Voltage at ‘A’ =I IA*ZAB + [IA+ID]*Zf ] 

ZAf   =  V at ‘A’ / IA 

         =  ZAB + [1+ ID / IA]*Zf

          =  ZA + Zf + [ ID / IA]*Zf

Impedance seen by the relay > actual impedance to the fault point.

The relay under reaches since this effect reduces the apparent reach measured by distance relays

Impedance seen by the relay at ‘D’

= ZBD + Zf +[IA / ID]*Zf

A distance relay is said to under-reach when the impedance presented to it is apparently greater than the impedance to the fault

Percentage under-reach is defined as:

where:

ZR = intended relay reach (relay reach setting)

ZF = effective reach

Zone 2 i.e Z2 at A must be set to overreach bus B for   in_feed at bus B and not to overreach bus D for no in_feed at bus B

Out_feed Overreach Effect

 

Usually associated with three terminal line applications and paralleling of line segment

Example as in above SLD:

VG = 2(1) + 2(1) = 4

ZG (Apparent) = VG / IG

ZG = 4/2 = 2 Ohm

Z1 will overreach and see the fault

A distance relay is said to over-reach when the impedance presented to it is apparently less than the impedance to the fault

where:

ZR = intended relay reach (relay reach setting)

ZF = effective reach

Tapped transformers and loads Under reach effect

VG = IG*mZL + ( IG + IH ) ZT

ZG (Apparent) = VG / IG

ZG = m*ZL + (1 + IH/IG) ZT

ZG = mZL + ZT + IH/IGZT (Increase in apparent   impedance)

Apparent impedance will always be larger than   impedance to fault.

Relay at G will under reach.

Lines terminated into transformers

IH and VH preferred to provide line protection

Use of VL and/or IL affects measured impedance and requires CT and/or VT  ratio adjustment

Transformer should always be protected separately

Source impedance ratio

Ratio of source impedance to the line impedance

SIR to the relay is the ratio of source impedance to the zone impedance setting

The higher the SIR the more complex the line protection  with zone 1

Measurement errors are more pronounced Current and or voltage transformer error CVT transients

Zone-1 may not be recommended in many applications and Current differential protection preferred

Switch onto fault logic

Logic determines breaker has been open awhile and sets SOTF logic (aka: CIFT, SOFT)

  • Breaker position
  • Dead line logic

When breaker controlled by relay A closes SOTF asserts when:

I and Not V, and/or SOTF operates

Set ZSOTF offset, overreaching line and below minimum load impedance

Three Terminal line Application

Zone 1 at A- 85% of the shorter line section 85% of Minimum of ZAB or ZAC

Zone 2 at A – 125% of the apparent impedance of the longest line section or

ZA + 1.25*ZC_apparent or 1.25(ZA + ZC_apparent)

=1.25*[ ZA +ZC(1 +IB/IA)]

Time Coordination

Relay at A: Zone 2- 125% ZAPP

Zone 2 = 1.25*[ZA+ZB*(1+IC/IA)]

Relay at B on B-D line:

Zone 1 -85% of ZB-D

When there is no infeed (breaker C open), the zone 2 relay reaches beyond terminal D

Zone 2 time delay needs coordination with relays at B on line B-D

Sequential Tripping

If the ratio of currents is high – ex-20:1 for IC/IA

Relay at A sees ZA+ZC(1+20)

Relay setting is too large

Allow stronger end ( End- C in this case) to trip first

Relay at A operates after breaker at C opens

Zone 2 or Zone 3 Settings

Overreaching zones should consider apparent impedance (Z2 for three terminal line)

Zone 3- 100% of the line +125% of apparent impedance of adjacent line

If it is not possible to set, sequential tripping could be utilized

Factors that influence Distance Relay settings & operation

Parallel Lines – Effect of Mutual impedance on ground distance elements

  • Current Reversal
  • Series compensated lines
  • Effect of load
  • Out of Step condition

Phase distance and Ground Distance Schemes

3 Phase distance and 3 ground distance element per zone

Phase distance & Ground overcurrent Schemes

Distance Elements to detect phase-phase and three   phase faults

Ground directional overcurrent relay to detect faults   involving ground

Zone coordination using distance & ground relays

Distance zones are time coordinated based on reach

Ground overcurrent relays (directional inverse time overcurrent relays) are also coordinated with time.

Fault clearing times on lines

Z1- Distance – Assume Zone 1 setting = 85% of line Z

All faults within 15-85% of the line are cleared by both end without any time delay.

Remote end faults (85-100% from end A) – cleared by Zone 2 with a time delay (typically 15-30 cycles)

Close-in faults (0-15%) from end A are cleared in zone 2 from line relay at end B

End-Zone Faults

0-15% from ends are cleared in zone 2 from remote ends

These are called end-zone faults

Total fault clearing time is equal to zone 2 time delay + breaker operating time

Pilot Schemes

  • Phase comparison Scheme
  • Current differential schemes
  •  Directional Comparison schemes using distance (or directional over current) relays

Communication Medium

  • Power line Carrier
  • Leased telephone line
  • Microwave
  • Fiber optic cable

Directional Comparison Scheme

Uses directional relays to determine fault position relative to the protected line and communicates that information to the remote terminal

The information is used to achieve faster tripping at both ends.

Terminology

ZUR -Underreaching Zone (Element) – Relay set to reach shorter than the total protected line

ZOR – Overreaching Zone (Element) – Relay set to reach longer than the total protected line

Various tripping schemes were originally designed with electromechanical relays and had distinctive names

Microprocessor relays combine various schemes with  same nomenclature

We will use Z1 for the ZUR and Z2 for ZOR

 

Direct under reach transfer trip transfer

Permissive  under reach transfer trip transfer

Issues With permissive  under reach transfer trip transfer For single-end fed close-up fault on double circuit line

Fault occurs close to A as shown. Bus A voltage low so negligible fault infeed from B end

End A CB Clears Fault and fault is then fed from end B

Issues With permissive  under reach transfer trip transfer For single-end fed close-up fault on double circuit line

Time delayed resetting of the PUR ‘signal received’  element is required (because other wise both zone1 at source end A and received signal at B end would reset   before fault reverses and Zone 2 at B end operates)

Time delayed resetting of received signal is required to ensure that the relays at both ends of a single-end fed  faulted line of a parallel feeder circuit have time to trip when the fault is close to one end

Time delayed resetting of the PUR ‘signal received’   element

PERMISSIVE OVER REACH TRANSFER TRIP SCHEME

PERMISSIVE OVER REACH TRANSFER TRIP SCHEME CURRENT REVERSAL GUARD IN PARALLEL DOUBLE END FED LINES WHERE ZONE 2 REACH IS SET GREATER THAN 150 % OF PROTECTED LINE

To prevent operation under current reversal conditions in  a parallel feeder circuit, a current reversal guard timer to is required to inhibit the tripping of the forward Zone 2 elements.

Otherwise maloperation of the scheme may occur under current reversal conditions

PERMISSIVE OVER REACH TRANSFER TRIP SCHEME CURRENT REVERSAL GUARD IN PARALLEL DUAL END LINES

For fault close to K end, protection at K clears fault faster than at J.. As soon as K end CB opens, the direction of  current in healthy feeder reverses. The Zone 2 at end G of healthy feeder had OPERATED and had  send signal to H when fault at K started gets   RESET when breaker at K opens to clear fault end H of healthy feeder that had RESTRAINED  when fault at K started OPERATES when breaker  at K opens to clear fault near it

If Zone 2 at H operates before Zone 2 at end G resets tripping of breakers on healthy feeder at G & H takes  place.  This is not a desirable tripping

The timer is used to block the permissive trip and signal send circuits as shown in next slide. The timer is  energised if a signal is received and there is no operation of Zone 2 elements.

An adjustable time delay on pick-up (tp) is usually set to  allow instantaneous tripping to take place for any internal faults, taking into account a possible slower operation of   Zone 2. The timer will have operated and blocked the ‘permissive trip’ and ‘signal send’ circuits by the time the  current reversal takes place.

 

Current reversal guard logic – permissive over-reach scheme

Weak Infeed Conditions

In the standard permissive over-reach scheme, as with the permissive under-reach scheme, instantaneous   clearance cannot be achieved for end-zone faults under weak infeed or breaker open conditions.

The Weak Infeed Echo feature available in some protection relays allows the remote relay to echo the trip signal back to the sending relay even if the appropriate remote relay element has not operated.

A time delay (T1) is required in the echo circuit to prevent tripping of the remote end breaker when the local breaker is tripped by the busbar protection or breaker fail protection associated with other feeders connected to the busbar.

The time delay ensures that the remote end Zone 2 element will reset by the time the echoed signal is   received at that end.

A variation on the Weak Infeed Echo feature is to allow tripping of the remote relay under the circumstances   described above, providing that an under voltage condition exists, due to the fault

Weak Infeed Trip feature and ensures that both ends are tripped if the conditions are satisfied.

Reverse Looking Zone

Could be Zone 3 or Zone 4 depending on the manufacturer

POTT logic is designed in the relay based on zone 3 or zone 4

GE- Zone 4 is the reverse looking element

SEL – Zone 3 is the reverse looking element

Reverse element is set to reach farther than the remote overreaching element (Zone 2)

If there is no current flowing on the line, Voltage at the fault will be same as the voltage at the relay.

If the system is not weak, Voltage at the relay location will be more that the voltage at the fault location.

The U/V setting has to be below the voltage seen under normal condition.

SEN EDS offers Engineering Consultancy, Detailed Engineering Services and Power System Engineering Services (ETAP & DIgSILENT & PSCAD) for Switchyard up to 400kV Substation, Port, Industrial Project (Oil and Gas Plant, Steel Plant, Thermal Power Plant, Cement Plant, Water Treatment Plant), Grid Impact Study and Grid Code Compliance (UK, Oman, KSA, UAE, etc.), Airport Project, Specializing in Renewable Energy (Solar and Wind with BESS Plant)

Copyright © 2024 – SEN EDS – All Rights Reserved.