Transformer LV Restricted earth fault Protection

Original price was: ₹500.00.Current price is: ₹400.00.

Calculations:
REF Function
This setting is used to select the principle used for the differential protection.
Transformer Rating = 2.00 MVA
Primary side (HV) = 33.00 kV
Secondary side (LV) = 0.415 kV
Impedance = 6.390 %
Rated current = 2782.89 Amps
CT ratio = 2782.89 Amps
CTRp = 3200
CTRs = 1
Therefore a current of 2782.49 Amps in Primary will reflect in secondary as
= 2782.41 / (3200 / 1)
= 0.87 Amps
Pick-up of the High Imp REF function in
secondary
= 20% of 0.87
Is1 = 0.17 A

Notes:

This document has been exclusively prepared by SENEDS. SENEDS will not be responsible for any discrepancies or errors found within the document. Once the document is purchased payments are non-refundable.

For any queries or clarifications, we kindly request that you refrain from calling or emailing us.

Transformer LV Restricted earth fault Protection

Original price was: ₹500.00.Current price is: ₹400.00.

Calculations:
REF Function
This setting is used to select the principle used for the differential protection.
Transformer Rating = 2.00 MVA
Primary side (HV) = 33.00 kV
Secondary side (LV) = 0.415 kV
Impedance = 6.390 %
Rated current = 2782.89 Amps
CT ratio = 2782.89 Amps
CTRp = 3200
CTRs = 1
Therefore a current of 2782.49 Amps in Primary will reflect in secondary as
= 2782.41 / (3200 / 1)
= 0.87 Amps
Pick-up of the High Imp REF function in
secondary
= 20% of 0.87
Is1 = 0.17 A

SEN EDS offers Engineering Consultancy, Detailed Engineering Services and Power System Engineering Services (ETAP & DIgSILENT & PSCAD) for Switchyard up to 400kV Substation, Port, Industrial Project (Oil and Gas Plant, Steel Plant, Thermal Power Plant, Cement Plant, Water Treatment Plant), Grid Impact Study and Grid Code Compliance (UK, Oman, KSA, UAE, etc.), Airport Project, Specializing in Renewable Energy (Solar and Wind with BESS Plant)

Copyright © 2024 – SEN EDS – All Rights Reserved.