GENERAL
 Assumptions & references:
1. Fault MVA corresponding to 40kA is approximately 450 MVA. Hence 450 MVA is
considered as base MVA for calculation purpose.
2. Transformer impedance is considered with 10% negative tolerance
 Result:
1. Manual Calculation
Fault at 6.6kV Bus: 19.01 kA
Fault at 415V Bus: 42.07 kA
2. ETAP
Fault at 6.6kV Bus: 18.50 kA
Fault at 415V Bus: 43.10kA
 Conclusion:
Both Manual & ETAP results are within the design fault level of 40kA for 1 sec at 6.6kV &
50 kA for 1 sec at 415 (433V)

Notes:

This document has been exclusively prepared by SENEDS. SENEDS will not be responsible for any discrepancies or errors found within the document. Once the document is purchased payments are non-refundable.

For any queries or clarifications, we kindly request that you refrain from calling or emailing us.

Short Circuit Calculation

Original price was: ₹600.00.Current price is: ₹500.00.

GENERAL
 Assumptions & references:
1. Fault MVA corresponding to 40kA is approximately 450 MVA. Hence 450 MVA is
considered as base MVA for calculation purpose.
2. Transformer impedance is considered with 10% negative tolerance
 Result:
1. Manual Calculation
Fault at 6.6kV Bus: 19.01 kA
Fault at 415V Bus: 42.07 kA
2. ETAP
Fault at 6.6kV Bus: 18.50 kA
Fault at 415V Bus: 43.10kA
 Conclusion:
Both Manual & ETAP results are within the design fault level of 40kA for 1 sec at 6.6kV &
50 kA for 1 sec at 415 (433V)

SEN EDS offers Engineering Consultancy, Detailed Engineering Services and Power System Engineering Services (ETAP & DIgSILENT & PSCAD) for Switchyard up to 400kV Substation, Port, Industrial Project (Oil and Gas Plant, Steel Plant, Thermal Power Plant, Cement Plant, Water Treatment Plant), Grid Impact Study and Grid Code Compliance (UK, Oman, KSA, UAE, etc.), Airport Project, Specializing in Renewable Energy (Solar and Wind with BESS Plant)